Hermetically sealed and conservator designs from 6 kV to 35 kV class, 30 to 4,000 kVA three-phase — plus single-phase pole-mounted units for rural electrification programs.

| Type | Rated capacity (kVA) | No-load loss (kW) | Load loss (kW) | Impedance (%) |
|---|---|---|---|---|
| S20-100/10 | 100 | 0.135 | 1.51 / 1.44 | 4.0 |
| S20-200/10 | 200 | 0.215 | 2.19 / 2.08 | 4.0 |
| S20-315/10 | 315 | 0.305 | 3.07 / 2.92 | 4.0 |
| S20-400/10 | 400 | 0.37 | 3.62 / 3.44 | 4.0 |
| S20-500/10 | 500 | 0.43 | 4.33 / 4.12 | 4.0 |
| S20-630/10 | 630 | 0.51 | 4.96 | 4.5 |
| S20-800/10 | 800 | 0.63 | 6.00 | 4.5 |
| S20-1000/10 | 1000 | 0.745 | 8.24 | 4.5 |
| S20-1250/10 | 1250 | 0.87 | 9.60 | 4.5 |
Load losses shown as both tapping extremes where applicable. Full loss tables for every series and voltage class — including amorphous-alloy units — are available on request as PDF datasheets.
Compact cylindrical transformers for direct pole mounting — the workhorse of rural electrification tenders across Africa.

Small footprint, low installed cost and simple handling make single-phase units ideal for low-density load areas. Custom dimensions and tap configurations can be produced against customer drawings.
We provide complete no-load / load loss tables, dimensions and weights for every series — plus sample type-test reports before you commit.